
Shear walls are very stiff vertical structural elements in framed structures designed primarily to resist lateral forces (e.g. wind). In-order words, they form the lateral stability system of braced frames. As a building increases in height, the influence of wind forces, seismicity and other forms of lateral loads becomes very significant. Thus, one of the methods of ensuring lateral stability and avoiding excessive lateral deflection is by deploying shear walls across the width of the building to resist the lateral forces.
The fundamental of lateral stability was a topic discussed in a previous post. See Fundamentals of Lateral Stability. It’s a prerequisite to this post, you are encouraged to read the post before going ahead with the content of this post.
Analysis of Shear Walls
Shear walls are analyzed as vertical cantilevers subjected to the lateral forces. It is always desired to ensure that the position of shear walls in the plan is symmetrical. This is to ensure that the centre of the stiffness (shear centre) of the structure coincides with the point of application of the lateral forces in order to avoid large torsional forces. However, in reality, this is not always possible as a result of architectural constraints. The walls must, therefore, be designed to withstand torsion due to eccentricity between the centre of the stiffness of the walls and the point of application of the loads.
The worked example presented in this post assumes symmetrical layout of shear walls. Where the layout is unsymmetrical, the effect of torsion must be considered. This is beyond the scope of this post, however, guidance can be found from the texts in the further reading section of the post.
Derivation of Actions on Shear Walls
In addition to resisting the lateral forces which are primarily in the plane of the wall. Shear walls are also required to resist axial forces and moment outside the plane of the wall. In fact, the derivation of actions as well as the design of shear walls is very similar to that of a concrete column.
Axial Forces
The axial forces on the wall can be calculated using an elastic method of analysis. The tributary area method can be used or the vertical reaction from a subframe analysis.
Transverse Moment
Transverse moment, is the moment perpendicular to the plane of the wall. Its magnitude can be calculated from the analysis of a subframe.
In-plane Moment
This is the moment in the plane of the wall due to the applied lateral loads, its magnitude is determined by treating the wall as a vertical cantilever and taking moment about the foot of floors. It is very common to have several shear walls resisting the lateral actions. This lateral forces will be apportioned to the walls according to their stiffness’s. Thus a stiffer wall will attract more load.
For example, consider the shear walls shown in figure one, connected by floor slabs a

Thus, since the walls are of equal heights, the load will be distributed between the walls in proportion to the second-moment area of the walls. i.e.
Where:
- F1 & F2 is the portion of wind action shared by wall one and wall two respectively.
- I1 & I2 is the second-moment area of wall one and wall two respectively.
- Fk is the wind action
Worked Example
Figure 2 shows the typical floor layout of an 8 storey office building. Wall A is 200mm thick and provides vertical support to the 200mm thick flat slab and lateral stability to the building in the plane of the wall. The characteristic permanent and variable actions on the roof are 6.0kN/m2 and 1.5kN/m2 respectively. While on the floors the permanent and variable actions are 7.5kN/m2 and 3.0kN/m2. The net wind pressure in the plane of this wall is 2.5kN/m2 Derive the actions required to design this wall at mid-height and at the base. Take the storey height = 3@8=24m
How to derive wind load on buildings has been covered in a previous post See: Derivation of Wind Loads on Buildings

This example assumes that second-order effects are negligible. For practical purposes, second-order effects must be checked before applying the procedures described in this post
Actions
- On the roof, the permanent actions gk=6.0kN/m2 while the variable actions
q k =1.5kN/m2 - On the floors, the permanent actions gk=6.0kN/m2 while the variable actions
q k =3kN/m2 - Net wind pressure =2.5kN/m2
Actions from Roof
Permanent Actions
Variable Actions
Actions from floors
Permanent Actions
Variable Actions
Imposed load reduction factors can be applied to the wall based on the numbers of storeys supported αn=1-n/10; where n=number of floors supported.
Floors | αn | Gk(kN) | G(kN) cum. | Qk(kN) | Qk(kN) cum. | Qk(kN) red. |
7-R | 1 | 215.6 | 215.6 | 35.2 | 35.2 | 35.2 |
6-7 | 0.9 | 239.1 | 454.7 | 65.6 | 100.8 | 90.7 |
5-6 | 0.8 | 239.1 | 693.8 | 65.6 | 166.4 | 133.1 |
4-5 | 0.7 | 239.1 | 932.9 | 65.6 | 232.0 | 162.4 |
3-4 | 0.6 | 239.1 | 1172 | 65.6 | 297.6 | 178.6 |
2-3 | 0.6 | 239.1 | 1141.1 | 65.6 | 363.2 | 217.9 |
1-2 | 0.6 | 239.1 | 1650.2 | 65.6 | 428.8 | 257.3 |
G-1 | 0.6 | 239.1 | 1889.3 | 65.6 | 494.4 | 296.6 |
Axial Actions
Since we’re required to determine the design actions at mid height and base of the wall, we have
At Mid Height
Assuming Imposed loading is the leading variable action and wind is the accompanying variable action.
Assuming wind loading is the leading variable action and imposed loading is the accompanying variable action.
At Base
Assuming Imposed loading is the leading variable action and wind is the accompanying variable action.
Assuming wind loading is the leading variable action and imposed loading is the accompanying variable action.
In-Plane Moments
By inspection, the walls are symmetrical about the plane of application of the wind actions. Therefore the shear centre of the wall will coincide with the point of application of the wind load, hence the effect of torsion can be neglected. Our in-plane moment is the overturning moment about the point at which it is desired.
The wind is being shared according to the stiffnesses of the walls
Therefore, the proportion of wind load taken by wall A is 32% of the total wind action. The wind action is converted to uniformly distributed load by multiplying the net wind pressure by the width of the building.
Overturning Moment
At Mid height
Assuming wind loading is the leading variable action and imposed loading is the accompanying variable action.
Assuming Imposed loading is the leading variable action and wind is the accompanying variable action.
At Base
Assuming wind loading is the leading variable action and imposed loading is the accompanying variable action.
Assuming Imposed loading is the leading variable action and wind is the accompanying variable action.
The effect of global imperfection needs to be considered. This is done by applying horizontal notional loads in addition to the applied wind loads. This has been neglected in this post. However, for practical purposes, its effect must be considered. This has been covered in a previous post. See: Application of Notional Loads on Structures.
Transverse Moment
The out of plane moment will be determined using an equivalent frame consisting of the floor at a level and the walls above and below it. The slab frames into the wall and for the purpose of assessing the fixed end
Figure 3 shows the subframe, note that the stabilizing effect of the stair has been ignored. This is conservative.

Moment
Assuming Imposed loading is the leading variable action and wind is the accompanying variable action.
Assuming wind loading is the leading variable action and imposed loading is the accompanying variable action.
Table 2 & 3 gives a summary of the design actions on the wall. The Actions required to design this wall has been determined. By inspection, load case 2 prooves more onerous and therefore could be used to design the wall.
Position | Axial Load (kN) | In-plane Moment (kN.m) | Transverse Moment (kN.m) |
Mid-height | 1503.2 | 1620 | 80.1 |
Base | 2995.5 | 6480 | 80.1 |
Position | Axial Load (kN) | In-plane Moment (kN.m) | Transverse Moment (kN.m) |
Mid-height | 1430.1 | 3240 | 72.7 |
Base | 2862 | 12960 | 72.7 |
Further Reading
- P Bhatt., T.J MacGinley., B.S Choo- Reinforced Concrete Design to Eurocodes (4th ed)-CRC Press.
- The Concrete Centre (2009) Worked Examples to Eurocode 2: Volume 1 [Online] http://www.concretecentre.com/pdf/ Worked_Example_Extract_Slabs.pdf (Accessed: March 2014).
THANKYOU!!! WATCH OUT FOR THE DESIGN OF THE WALL
760616 407449when i was a kid, i love to receive an assortment of birthday presents like teddy bears and mechanical toys, 416570
404301 241399I like what you guys are up also. Such intelligent function and reporting! Maintain up the superb works guys Ive incorporated you guys to my blogroll. I believe itll improve the value of my web site . 701490
869943 195264Music started playing when I opened this webpage, so annoying! 327588
557139 77870I feel your suggestion would be valuable for me. I will let you know if its function for me too. Thank you for sharing this beautiful articles. thanks a lot 425789
836753 840699Discover how to deal along with your domain get in touch with details and registration. Understand domain namelocking and Exclusive domain name Registration. 821307
819126 561708Excellent blog here! Also your web internet site loads up quick! What host are you employing? Can I get your affiliate link to your host? I wish my site loaded up as swiftly as yours lol 432141
232612 515887Thoughts talk within just around the web control console video clip games have stimulated pretty professional to own on microphone as properly as , resemble the perfect tough guy to positively the mediocre ones. Basically fundamental troubles in picture gaming titles. Drug Recovery 433980
902408 589516Totally composed content material material , thankyou for information . 156471
I got tagen slots web page from my friend who informed me about tagen slots slot online and
at the moment tagen slots time I am visiting tagen slots web page and reading very informative
content at tagen slots place.